DIALOG PLUS
9 - OPTIONS
> 9.1 Summary table of the options available
DESCRIPTION DIMENSIONS (HxWxD mm) WEIGHT ( KG )
Isolating transformer module for
DLP 100/DLP 150
480x158x348 22
Isolating transformer module for
DLP200/DLP300
480x158x348 30
PowerShield
2
communication
software (“full” version)
Remote display panel with led
ISOLATING TRANSFORMER MODULE:
Enables the UPS output to be galvanically isolated from the input.
Enables the user to modify the neutral regime (for example, from TT to TN, or from TT to IT) to increase the
continuity of the power supply (IT systems) or to increase the level of protection to the users (TN systems).
The transformer may be connected to the input or to the output of the UPS.
> 9.2 Installation of the battery expansion module
> 9.2.1. Configuration of the battery expansion module
Following the installation of one or more battery expansion modules, the correct total Ah value must be
entered into the UPS memory. This may be done by using the UPSTools program, which can be found on
the same disc as the UPS management software, once this has been installed correctly.