SPEDLPX0205REN
29
DIALOG PLUS
MODEL 700VA 1000VA 1000VA ER 1500VA 2000VA 2000VA ER 3000VA 3000VA ER
Frequency variation
velocity (Hz/sec.)
1 Hz/s
Voltage reset after
dynamic variation
<20 ms
Voltage distortion
(linear load)
<2 %
Voltage distortion
(non-linear load)
<6 %
OVERLOAD TIMES
INVERTER OVERLOAD WITH MAINS SUPPLY AVAILABLE
100%<Load<110% 30 ‘
110%<Load<150% 30 ’’
Load > 150% 10 ‘’
VARIOUS
AC/AC efficiency (double
conversion operation)
90 %
Maximum permanent
operating temperature
40°C
Ambient operating
temperature
40°C
Recommended operating
temperature (for the
batteries)
20/25°C
Humidity
<95% without condensation
Protections Excessive battery discharge – overcurrent – short-circuit – overvoltage – undervoltage - over temperature
Compliance with safety
regulations
EN62040 -1-1
Directives 73/23/EEC and 93/68/EEC
EMC compliance EN50091 -2 cl. A, directive 89/336/EEC
Noise <40 dB (A) at 1 metre
DIMENSIONS
Height (mm) 236 236 236 236 348 348 348 348
Width (mm) 158 158 158 158 192 192 192 192