Start-up, calibration and operation of the burner
5
List of the parameters that can be visualised (in the sequence
in which they are visualised)
Visualises the general system information.
The list of the parameters that can be visualised is given in
the table below.
To access this level, press the key “i/reset” for 1 - 3 s.
Release the key immediately when the display shows “Info”.
167 Volumetric delivery of fuel in the unit of measurement
selected
162 Operation time with flame
163 Operation time
164 No. of resettable ignitions
166 Total no. of ignitions
113 Identification code of the burner
107 Software version
102 Control box test date
103 Identification code of the control box
104 Identification number of the group of parameters set
105 Version of the group of parameters
143 Reserved
End
Info Mode
1..3 s
P
m³ / h
l l / h
%
D7718
/reset
D8273
List of the parameters that can be visualised (in the sequence
in which they are visualised)
Visualises the log of errors and some technical information
regarding the system.
The list of the parameters that can be visualised is given in
the table below.
To access this level, press the “i/reset” key for more than 3 s.
Release the key immediately when the display shows “SEr”.
954 Flame intensity (%)
121 Manual setting of output
Not defined = automatic operation
922 Position of the servomotors (expressed in degrees,
symbol )
0 = fuel
1 = air
161 Number of errors
701
.
.
.
725
Log of the errors: 701-725.01, Code
Service Mode
> 3 s
P
/ h
l
l/h %
D7719
/reset
D8273
Operating procedure in Info and Service Modes
After access to these levels, the display visualises the number of the parameter
(flashing) on the left, and the corresponding value on the right.
If the value is not visualised, press the key “i/reset” for 1 - 3 s.
To return to the Parameters List, press the key “i/reset” for more than 3 s, or press
simultaneously the keys “+” and “-” (esc).
To move on to the next parameter, press the key “+” or “i/reset” for less than 1 s. At
the end of the list, the display visualises “End”.
To move back to the previous parameter, press the key “-”.
To return to the Normal/Standard Visualisation Mode, press the “i/reset key for
more than 3 s, or press simultaneously keys “+” and “-” (esc). For a moment the
display will show “OPErAte”.
D7720
P
/ h
ll/h%
From Normal Mode, using the keys of the Operator Panel, it is possible to activate one of the three visualisation/programming modes:
Info Mode (InFo)
Service Mode (Ser)
Service Mode (Ser)
V
isualisation modes
Programming modes
1
2
3